Bluenergy Elect oil N-42 Inhibited transformers oils are severely refined hydro-cracked / hydro-treated virgin un-inhibited Naphthenic insulating oils with highest degree of purity and stability. It is manufactured from judiciously selected blend of latest technology feed stocks, which is highly suitable for all grades of Power & distribution Transformers, Circuit Breakers, Oil filled switches and X-ray equipment.
Description
Features & Benefits
- Very low Sulphur and no DBDS.
- Low Pour point.
- High dielectric strength.
- Non corrosive as tested by all present methods, DIN & ASTM tests & New IEC 62535 method.
- Low viscosity oils offering excellent and fast heat transfer.
- Higher Flash point, resulting on Low evaporation losses and better safety
- Remarkably low sludge and acidity formation, in both ageing and oxidation tests, results in longer life of oil and equipment
- Compatible with transformer construction material.
APPLICATION
- Bluenergy Elect oil N-42 Inhibited transformers oils are highly suitable for all grades of
- Power Transformers, Distribution Transformers
Circuit Breakers
- Oil filled switches
- X-ray equipment
SPECIFICATIONS
Bluenergy Elect oil N-42 Inhibited transformers oils conforms to and exceed the requirements of ASTM D 3487 Type II & IEC 60296:2012.
TYPICAL PHYSICAL CHARACTERISTICS
| Test Description | Test Method | Units | Specification Limits |
| Kinematic Viscosity 40 °C | ISO 3104 | mm2/s, max | 12 |
| Kinematic Viscosity -30 °C | ISO 3104 | mm2/s, max | 1800 |
| Pour Point | ASTM – D1400 | °C, max | <=-40 |
| Water Content, Bulk | IEC 60814 | mg/kg, max | 30 |
| Water Content, Drum | IEC 60814 | mg/kg, max | 40 |
| Density at 20 °C | ISO 3675 | 0.895 | |
| Break Down Voltage As delivered | IEC 60156 | kv/min | 30 |
| Break Down Voltage After treatment | IEC 6015 | 70 | |
| DDF @90 °C | IEC 60247 | °C, max | 0.005 |
These characteristics are typical of current product methods whilst future production will confirm to Bluenergy lubricants specifications, variations in these physical characteristics may occur.
NOTE:
Bluenergy Elect oil N-42 Inhibited transformers oils are High Grade Inhibited Transformer oil has superior oxidation stability – meeting the high-grade requirements as specified in IEC 60296:2012, high dielectric strength and are used in equipment requiring operations at high elevated temperatures & greater oxidation resistance.
PACKAGING OPTIONS:
Bluenergy Elect oil N-42 Inhibited transformers oils are offered in 200-210 liters of steel drums and also in bulk in Flexi bags or ISO tanks.
STORAGE PRECAUTIONS:
Extreme care is taken while packing these products, including filling of drums in inert atmosphere, as Electrical Insulating oils / Transformer oils are very sensitive to very minute concentrations of contaminants, such as moisture, particulate matter, fibers, etc. Hence, care should be taken to store Bluenergy Elect oil N-42 Inhibited transformers oils in a clean and dry condition. It is strongly recommended that all storage tanks / drums be maintained such that oil is not in contact with atmospheric air. Also these oils should always be stored indoors in climate-controlled environments.